The SIRIUS circuit breaker 3RV2031-4WA10 from Siemens in size S2 is a compact, current-limiting circuit breaker for load feeders up to 22 kW at AC-3/400 V. Due to a short-circuit protection of 741 A and an adjustable overload protection of 42 - 52 A, the circuit breaker is ideally suited for the protection of motors.
| Adjustment range undelayed short-circuit release | 741 A |
| Compliance/Standards | IEC 61508-2, IEC 61508, IEC 60529, EN 60715, IEC 60068-2, IEC 81346-2 |
| country_of_origin | Germany |
| Degree of protection (IP) | IP20 |
| Depth | 149 mm |
| description | Circuit breaker size S2 for motor protection, CLASS 10 A-release 42...52 A N-release 741 A screw terminal Standard switching capacity |
| Device construction | Built-in device fixed built-in technique |
| Height | 140 mm |
| IP Rating | IP20 |
| IP Rating Detailed | IP20 touch protection on the front according to IEC 60529 finger |
| Number of poles | 3 |
| Overload release current setting | 52 A |
| Part Depth (mm) | 167,00mm |
| Part Height (mm) | 147,00mm |
| Part Width (mm) | 62,00mm |
| Phase failure sensitive | Yes |
| Power loss | 24.5 W |
| Rated operating voltage | 690 V |
| Rated operation power at AC-3, 230 V | 15 kW |
| Rated operation power at AC-3, 400 V | 22 kW |
| Rated permanent current Iu | 52 A |
| Rated short-circuit breaking capacity lcu at 400 V, AC | 65 kA |
| Switch off technique | Magnetic |
| Type of control element | Other |
| Type of electrical connection of main circuit | Screw connection |
| Weight (g) | 1,164 Kg |
| Width | 55 mm |
| With thermal overload protection | Yes |
Complete technical specifications (PDF)
Product brochure and catalog information
Installation and operation guide
Wiring and connection guide
Compliance and certification documents
Mechanical dimensions and mounting
3D models and CAD files
Manufacturer product page and specifications
Product approvals and certificates
Environmental Product Declaration
Full specifications, datasheets and downloads
Overview, features and application examples