This 4-pole contactor combines 2NO + 2NC contacts with a 220VAC coil, suited to switching and control duties within control panels. It is rated at 80A (at under 60°C) for AC-1 applications up to 690V AC on the power circuit, with screw clamp terminals accepting a range of cable sizes and types for both control and power connections. The enclosure carries an IP20 rating on the front face, and the unit measures 85mm wide, 127mm high and 125mm deep, making it suitable for compact panel installations.
Key specifications
| IP Rating / Detailed | IP20 front face conforming to IEC 60529 |
| Compliance/Certifications | CSA C22.2 No 14,EN 60947-4-1,EN 60947-5-1,IEC 60947-4-1,IEC 60947-5-1,UL 508 |
| Part Depth (mm) | 125mm |
| Part Width (mm) | 85mm |
| Part Height (mm) | 127mm |
| Connection Type | Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end,Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end,Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end,Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end,Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end,Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end,Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: flexible without cable end,Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: flexible without cable end,Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: flexible with cable end,Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: flexible with cable end,Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: solid without cable end,Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: solid without cable end |
| Rated Operating Voltage | Power circuit: <= 690 V AC 25...400 Hz |
| Current Rating | 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
| Power Consumption | in VA |
| Operating Period(Mech) | 6 Mcycles |
| Operating Period(Elec) | 1.4 Mcycles 80 A AC-1 at Ue <= 440 V |