Product Description

Product Overview

The Siemens 5SM6021-2 is an arc-fault detection device (AFDD) block designed for installation with circuit-breakers or RCBOs in single-phase + neutral (1 P + N) configurations. It is rated for 1-16 A in a 230 V network and forms part of Siemens’ SENTRON protection-component range, providing early detection of hazardous arcing faults and disconnection before fire risk arises.

Key Features

  • Arc-fault detection unit block (AFDD) compatible with MCBs and RCBOs
  • Dedicated for 1 P + N installation in 230 V AC systems
  • Rated current range: 1 A up to 16 A
  • Designed to detect series and parallel arcing faults and disconnect to prevent fire hazards
  • Installable supplementary device (block) for use with SENTRON MCBs or RCBOs
  • Width: 1 modular unit (18 mm), suitable for DIN-rail mounting
  • Halogen-free and silicon-free housing for safer installations

Technical Specifications

  • Product Series: SENTRON Arc-Fault Detection Device
  • Article Number: 5SM6021-2
  • Poles: 2 (1 P + N)
  • Rated Supply Voltage: 230 V AC, 50 Hz
  • Rated Current Range: 1 … 16 A
  • Installation Depth: approx. 70 mm
  • Width: 18 mm (1 module)
  • Ambient Operating Temperature: –25 °C … +45 °C
  • Protection Class: IP20 when installed with conductors

Compliance & Certifications

  • Manufactured by Siemens as part of the SENTRON protective-component portfolio
  • Developed for compliance with fire-safety and electrical-installations standards for arc-fault detection
  • Designed to expand standard overcurrent and earth-leakage protection with arc or fire hazard detection

Applications

Ideal for enhancing protection of residential or commercial branch circuits by adding arc-fault detection to standard circuit-breakers or RCBOs. Commonly used in installations where risk of insulation damage, loose contacts, or cable faults may lead to dangerous arcing and fire—such as lighting circuits, outlet circuits, consumer-unit upgrades, and retrofit protection solutions.

Technical Specifications

Built-in depth70 mm
Control voltage type auxiliary equipmentAC
Degree of protection (IP)IP20
Frequency50 Hz
Number of poles2
Over voltage category3
Pollution degree2
Rated current16 A
Rated voltage230 V
Voltage typeAC
Width in number of modular spacings1