Siemens

Siemens Circuit breaker, line protection, 4-pole, 55kA, 415V, 160A Part number 3VA1116-5ED46-0AA0

EAN / Barcode 4042948822883
Product Type Control Panel
Product Class Power circuit-breaker for trafo/generator/installation protection
ETIM Class Power circuit-breaker for trafo/generator/installation protection
Back Order
View Full Product Details on Siemens 💬 Ask an Expert - Technical Support Available

Product Description

Product Overview

Circuit breaker 3VA1 IEC Frame 160 breaking capacity class M Icu=55 kA @ 415 V 4-pole, line protection TM210, FTFM, In=160 A overload protection Ir=160 A permanently set short-circuit protection Ii=10 x In N conductor unprotected terminal connection.

Article Number: 3VA1116-5ED46-0AA0

Technical Specifications

Product Lifecycle: PM300:Active Product

Net Weight: 1.347 kg

Packaging Dimensions: 119.00 x 150.00 x 116.00 mm

Quantity Unit: 1 Piece

Packaging Quantity: 1

EAN: 4042948822883

UPC: 804766428005

Country of Origin: Czech Republic

Compliance Information

Export Control Regulations: AL : N / ECCN : 9N9999

RoHS Compliance: Since 01.04.2014

Product Class: C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.

WEEE Take-Back Obligation: Yes

REACH Article 33: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0.1% weight by weight (w/w): Lead. Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classification Standards

  • eClass: 27-37-04-09
  • ETIM: EC000228
  • UNSPSC: 39-12-16-01

Download existing graphical data for this product:

Technical Datasheet (PDF)

Technical Specifications

Adjustment range undelayed short-circuit release1600 A
Complete device with protection unitYes
Degree of protection (IP)IP40
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalYes
Motor drive optionalYes
Number of poles4
Overload release current setting160 A
Position of connection for main current circuitFront side
Power loss38 W
Rated permanent current Iu160 A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz55 kA
Rated voltage690 V
Suitable for DIN rail (top hat rail) mountingYes
Type of control elementRocker lever
Type of electrical connection of main circuitFrame clamp
Part Width119 mmmm
Part Height150 mmmm
Part Depth116 mmmm
Weight1347 gg
Country of OriginCzech Republic
View complete specifications on Siemens

Videos & Media

Product Overview

Overview, features and application examples