This limit switch body provides snap action switching with one normally closed and one normally open contact. It forms part of a limit switch assembly used to detect the position or presence of machine components, triggering a control signal when actuated. Typical applications include end-of-travel detection and interlocking on industrial machinery within automation panels.
| Product data sheet | ZCKS1H29 |
| Characteristics | limit switch body ZCKS - 1NC+1NO - snap action - M20 |
| Range of product | OsiSense XC |
| Series name | Standard format |
| Product or component type | Limit switch body |
| Device short name | ZCKS |
| Body type | Fixed |
| Product compatibility | XCKS |
| Associated head | ZCKD06 ZCKD91 ZCKD81 ZCKD029 ZCKD39 ZCKD31 ZCKD41 ZCKD49 ZCKD33 ZCKD54 ZCKD01 ZCKD08 ZCKD34 ZCKD02 ZCKD59 ZCKD55 ZCKD05 ZCKD019 |
| Body material | Plastic |
| Cable entry | 1 entry tapped for M20 x 1.5 cable gland |
| Number of poles | 2 |
| Contacts type and composition | 1 NC + 1 NO |
| Contact operation | Snap action |
| Number of steps | 1 1 position |
| Contacts material | Silver plated contacts |
| Jan 1, 2020 | 1 |
| Local display | Without |
| Positive opening | With |
| Minimum actuation speed | 0.01 m/min |
| [Ie] rated operational current | 3 A at 240 V, AC-15, A300 conforming to EN/IEC 60947-5-1 appendix A 0.27 A at 250 V, DC-13, Q300 conforming to EN/IEC 60947-5-1 appendix A |
| [Ithe] conventional enclosed thermal | 10 A |
| Maximum resistance across terminals | 0.25 mOhm conforming to IEC 60255-7 category 3 |
| [Uimp] rated impulse withstand | voltage 6 kV IEC 60664 6 kV IEC 60947-1 |
| Short-circuit protection | 10 A cartridge fuse, type gG |
| Width | 40 mm |
| Height | 73 mm |
| Depth | 36 mm |
| Net weight | 0.08 kg |
| Terminals description ISO n°1 | (11-12)NC (21-22)NC |
| IP degree of protection | IP65 |
| IK degree of protection | IK03 |
| Ambient air temperature for operation | -25…70 °C for standard environment |
| Ambient air temperature for storage | -40…70 °C |