| Product data sheet | LV525333 |
| Characteristics | Easypact CVS - CVS250F TM250D circuit breaker - 3P/3d |
| Range of product | Easypact CVS100...250 |
| Product or component type | Circuit breaker |
| Device short name | CVS250F |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3d |
| Earth leakage protection (Vigi | add on) Without |
| [In] rated current | 250 A ( 40 °C ) |
| Breaking capacity code | F |
| Network type | AC |
| [Icu] Breaking capacity | 36 kA Icu conforming to IEC 60947-2 at 440 V AC 50/60 Hz |
| Utilisation category | Category A |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit rating | 250 A ( 40 °C ) |
| Protection type | Overload protection (thermal) Short-circuit protection (magnetic) |
| Network frequency | 50/60 Hz |
| Control type | Toggle |
| Mounting mode | Fixed |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Connections - terminals | Screw connection |
| [Uimp] rated impulse withstand | voltage 8 kV conforming to EN/IEC 60947-2 |
| Oct 10, 2018 | 1 |
| Thermal protection adjustment | range 0...250 A |
| [Ics] rated service breaking capacity | 18 kA conforming to IEC 60947-2 440 V AC 50/60 Hz |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles conforming to IEC 60947-2 415 V In |
| Connection pitch | 35 mm |
| Contact position indicator | Yes |
| Long time pick-up adjustment | type Ir Adjustable |
| Long time delay adjustment type | Fixed |
| Short-time delay adjustment type | Fixed |
| Instantaneous pick-up adjustment | type Fixed |
| Height | 161 mm |
| Width | 105 mm |
| Depth | 86 mm |
| Electrical shock protection class | Class II |
| Standards | EN 60947-2 IEC 60947-2 |
| Product certifications | GOST IEC |
| IP degree of protection | IP40 |
| Ambient air temperature for operation | -25...70 °C |
| Ambient air temperature for storage | -50...85 °C |