This is a 3-pole circuit breaker fitted with a TM-D thermal-magnetic trip unit, rated at 125A. It provides overcurrent and short-circuit protection for connected circuits, disconnecting supply when fault conditions are detected. Devices of this type are typically installed in distribution boards and control panels to protect feeders and downstream equipment.
| Range | EasyPact |
| Range of product | EasyPact CVS100...250 |
| Product name | EasyPact CVS |
| Device short name | CVS160F |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| Earth leakage protection (Vigi add | Without |
| [In] rated current | 125 A at 40 °C |
| Network type | AC |
| Utilisation category | Category A |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit rating | 125 A at 40 °C |
| Protection type | Overload protection (thermal) Short-circuit protection (magnetic) |
| [Uimp] rated impulse withstand | 8 kV conforming to EN/IEC 60947-2 |
| Network frequency | 50/60 Hz |
| Breaking capacity code | F |
| [Ics] rated service breaking | 18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| capacity | 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 25000 cycles |
| Electrical durability | 12000 cycles 415 V In conforming to IEC 60947-2 |
| Control type | Toggle |
| Thermal protection adjustment | 87.5…125 A |