The 3RV2011-4AA10 is a premium circuit breaker engineered for motor protection applications requiring the highest current ratings available in the S00 size category. This top-tier device delivers exceptional overload and short-circuit protection with a CLASS 10 A-release rating of 10...16 A and the maximum N-release of 208 A, featuring reliable screw terminal connections and standard switching capacity for the most demanding industrial applications.
Maximum Current Capacity: Provides the highest current rating available in S00 size (10...16 A), designed for the largest motors that can be accommodated in the compact 45mm form factor.
Superior Short-Circuit Protection: Features the highest N-release rating of 208 A in the S00 category, delivering unmatched short-circuit protection for the most demanding applications and high-performance motor systems.
Premium Screw Terminal Technology: Proven screw terminal connections ensure maximum reliability and secure electrical connections for critical high-current applications.
Compact High-Capacity Design: Size S00 form factor (45mm width) delivers maximum protection capability while maintaining the smallest possible footprint for space-critical installations.
Industrial Premium Construction: Built for the most demanding industrial environments with superior reliability, robust construction, and consistent high-performance characteristics.
Electrical Ratings:
Physical Characteristics:
Connection Specifications:
Environmental Specifications:
Maximum Current Motor Protection: Specifically engineered for protecting three-phase motors with ratings from 10-16A, providing both overload and short-circuit protection for the largest motors accommodated in S00 size.
High-Performance Industrial Systems: Ideal for demanding industrial applications including heavy-duty machinery, large industrial pumps, high-capacity conveyor systems, and critical manufacturing equipment.
Critical Infrastructure Protection: Perfect for applications where maximum protection is essential in a compact form factor, such as critical infrastructure, automated production lines, and precision industrial processes.
Premium Motor Applications: Designed for high-performance motors with demanding startup characteristics, elevated inrush currents, and applications requiring the highest level of short-circuit protection available.
Mounting Options:
High-Current Connection Requirements:
Clearance Requirements:
Advanced Overload Protection: Adjustable current setting from 10-16A provides precise protection for high-current motors while maintaining CLASS 10 tripping characteristics for reliable operation.
Maximum Short-Circuit Protection: Enhanced 208A N-release provides the highest level of protection against short-circuit conditions available in S00 size, ensuring safe disconnection and equipment protection.
Thermal Management: Temperature-compensated overload release with enhanced thermal characteristics ensures consistent protection across the full operating temperature range.
Phase Loss Sensitivity: Integrated phase loss detection prevents motor damage from unbalanced supply conditions and phase failures, critical for high-current applications.
Maximum S00 Capability: Offers the highest current rating available in the compact S00 form factor, eliminating the need to move to larger sizes for currents up to 16A.
Space Optimization: Delivers maximum protection capability while maintaining the smallest possible footprint, ideal for space-constrained installations.
Cost-Effective Solution: Provides premium protection without requiring larger, more expensive devices for currents within the 10-16A range.
Future-Proof Design: Accommodates motor upgrades and system expansions within the current rating range without device replacement.
Available Accessories:
System Integration:
Enclosure Options:
Current Rating Selection: Ideal for motors with rated currents between 10-16A, providing optimal protection without oversizing the protective device.
Thermal Management: Ensure adequate ventilation and ambient temperature control for optimal performance at maximum current ratings.
Conductor Sizing: Use appropriate conductor sizes for the full current range to ensure safe and reliable operation.
Technical Documentation:
CAD and Engineering Data:
Certificates and Compliance:
Additional Resources:
IP Rating | IP20 |
Country of Origin | Germany |
Temperature: Operating | -20°C to 60°C |
Part Depth (mm) | 97mm |
Part Width (mm) | 45mm |
Part Height (mm) | 97mm |
Weight (g) | 356g |
Packaging size / unit | 1 pc(s) |
Tightening Torque | 0.8 - 1.2 N·m |
Screw Type | Diameter 5 to 6 mm / Pozidriv size 2\r |
Connection Style | screw-type terminals |
Voltage Frequency Range | 50 / 60 Hz |
Mounting Type | Screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715 |
Current Rating / Rated Current | 16 A |
Operating Period | Product Lifecycle - PM300:Active Product |