This is a 3-pole contactor with 3NO contacts and a 24VDC coil, rated 95A (AC-3) at up to 440V AC for the power circuit, with a power circuit rating extending to 690V AC. It is used for switching motor loads and other industrial power circuits within control panels. The unit provides IP20 protection on the front face and terminates via screw clamp connections, suiting installation in enclosed switchgear and motor control centres.
Key specifications
| IP Rating / Detailed | IP20 front face conforming to IEC 60529 |
| Compliance/Certifications | EN 60947-4-1,EN 60947-5-1,IEC 60947-4-1,IEC 60947-5-1,CSA C22.2 No 14,UL 60947-4-1,IEC 60335-2-40:Annex JJ,UL 60335-2-40:Annex JJ,IEC 60335-1:Clause 30.2 |
| Part Depth (mm) | 186mm |
| Part Width (mm) | 85mm |
| Part Height (mm) | 127mm |
| Connection Type | Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end,Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end,Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end,Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end,Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end,Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end,Power circuit: connector 1 4…50 mm² - cable stiffness: flexible without cable end,Power circuit: connector 2 4…25 mm² - cable stiffness: flexible without cable end,Power circuit: connector 1 4…50 mm² - cable stiffness: flexible with cable end,Power circuit: connector 2 4…16 mm² - cable stiffness: flexible with cable end,Power circuit: connector 1 4…50 mm² - cable stiffness: solid without cable end,Power circuit: connector 2 4…25 mm² - cable stiffness: solid without cable end |
| Rated Operating Voltage | Power circuit: <= 690 V AC 25...400 Hz |
| Current Rating | 95 A (at <60 °C) at <= 440 V AC-3 for power circuit,125 A (at <60 °C) at <= 1000 V AC-1 for power circuit,95 A (at <60 °C) at <= 440 V AC-3e for power circuit |
| Power Consumption | in W |
| Operating Period(Mech) | 10 Mcycles |
| Operating Period(Elec) | 1.2 Mcycles 95 A AC-3,1.3 Mcycles 125 A AC-1,1.2 Mcycles 95 A AC-3e |